HIP3300 series UPS is developed as a high frequency large capacity tower UPS which adopting similar modular design , excellent performance parameters, more higher efficiency, more reliable, maily used in medium and large data center, bank/security settlement center, dispatching center, control center, management center fields and so on.
General Features
● DSP-controlled technology
● Parallel redundancy up to 4 units
● Wide input voltage and frequency range
● Easy-to-operate LCD display
● High power density up to 500kVA for space saving
● High input power factor and low input distortion
● Output power factor at 0.8(0.9 optional)
● ECO mode for energy saving
● Common or separate battery
● Programmable battery voltage from ±192Vdc to±240Vdc
● Intelligent charge modes with smart charge current adjustment
● Megatec/ModBus protocol supported
● Powerful charger built in
● Versatile communication interfaces provided for different applications
● Superior overload capability
● Programmable control and monitoring software
Technical Specification
MODEL | HIP3301 S/H |
HIP33015 S/H |
HIP3302 S/H |
HIP3303 S/H |
HIP3304 H |
HIP3306 H |
HIP3308 H |
|
Capacity (VA/Watts) |
10k / 8k | 15k / 12k | 20k / 16k | 30k / 24k | 40k / 32k | 60k / 48k | 80k / 64k | |
INPUT | ||||||||
Nominal voltage | 380/400/415Vac(3Ph+N+PE) | |||||||
Operating voltage range | 208~478Vac for half load; 305~478Vac for full load | |||||||
Operating frequency range | 40~70Hz | |||||||
Power factor | ≥0.99 | |||||||
Harmonic distortion(THDi) | 2%(100% non-linear load) | |||||||
Bypass voltage range | 380Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 400Vac Max.voltage: +20% (optional +10%,+15%) 415Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
|||||||
Bypass frequency range | Frequency synchronize tracing range:±10% | |||||||
Generator access | Support | |||||||
OUTPUT | ||||||||
Rated voltage | 380/400/415Vac(3Ph+N+PE) | |||||||
Power factor | 0.8/0.9(Customized) | |||||||
Voltage regulation | ±1% | |||||||
Frequency | Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | ||||||
Bat. mode | (50/60±0.2%)Hz | |||||||
Crest factor | 3:1 | |||||||
Harmonic distortion (THDv) |
≤2% with linear load ≤5% with non-linear load |
|||||||
Efficiency | 94.50% | 95.00% | ||||||
BATTERY | ||||||||
Battery voltage | Standard unit: ±216Vdc; Long run unit optional voltage: ±192 / ±204 / ±216 / ±228 / ±240Vdc | |||||||
Charging current(A) (Charging current can be set according to battery capacity installed) |
5.7A (Max./Standard unit) 6.0A (Max./Long run unit) |
12A (Max.) | 18A (Max.) | |||||
SYSTEM FEATURES | ||||||||
Transfer time | Utility to battery:0ms; Utility to bypass:0ms | |||||||
Overload | Line mode | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately | ||||||
Bat. mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | |||||||
Short circuit | Hold whole system | |||||||
Overheat | Line mode: Switch to bypass; Backup mode: Shut down UPS immediately | |||||||
Low battery voltage | Alarm and switch off | |||||||
Self-diagnostic | Upon power on and software control | |||||||
EPO (optional) | Shut down UPS immediately | |||||||
Battery | Advanced battery management | |||||||
Noise suppression | Complies with EN62040-2 | |||||||
Audible & Visual | Line failure, Battery low, Overload, System fault | |||||||
Status LED & LCD display |
Line mode, Bypass mode, Battery low, Battery bad, Overload & UPS fault | |||||||
Reading on the LCD display |
Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage & Inner temperature |
|||||||
Communication interface |
RS232,RS485,Parallel,Intelligent slot,Relay card(optional),SNMP card(optional) | |||||||
ENVIRONMENT | ||||||||
Operating temperature |
0~40℃ | |||||||
Storage temperature |
-25~55℃(No battery) | |||||||
Humidity range | 0~95% (Non-condensing) | |||||||
Altitude | <1500m. When >1500m, derating power for use | |||||||
Noise level | <55dB | |||||||
PHYSICAL | ||||||||
Dimension D×W×H (mm) |
780×600×1200 | |||||||
Net weight (kg) | S:598 H:129 |
S:600 H:131 |
S:602 H:133 |
S:603 H:134 |
170 | 172 | 199 | |
STANDARDS | ||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |