YDC3300
10-20kVA
YDC3300 series UPS compliant with UL/CSA standards is aviable now! Equipped with three-level inverter topology, it results in high energy-saving and reliability. With higher power density, smaller footprint, it takes the leading position in the UPS industry with same power capacity; Adopting unique power unit redundancy design technology, decrease the abnormity risk of system after single-point failure, greatly increase the system reliability. For user, it is your best choice with high investment rate.
Features
·High power density design
·N+Xparallel redundancy, maximum 4 units
.Onlline double conversion with DSP contro
.Cold start
·Wide input voltage range:72~159Vac .
·Multiple protection function:short-circuitoverload,overheat
Technical Specification
MODEL | YDC3310S/H | YDC3315S/H | YDC3320S/H | |
Capacity | 10kVA / 10kW | 15kVA / 15kW | 20kVA / 20kW | |
INPUT | ||||
Nominal voltage | 208/120Vac or 220/127Vac (3Ph+N+PE) | |||
Operating voltage range | 96~159Vac (Full load); 72~159Vac (50% load) | |||
Operating frequency range | 40~70Hz (50/60Hz Auto-Sensing) | |||
Power factor | ≥0.99 | |||
Bypass voltage range | Max. voltage: +20% (Optional +10%, +15%, +20%) Min. voltage: -30% (Optional -10%, -20%, -30%) | |||
Frequency protection range | 50/60Hz±10% | |||
ECO range | Same as bypass | |||
Harmonic distortion (THDi) | ≤2% Non linear load | |||
OUTPUT | ||||
Output voltage | 208/120Vac or 220/127Vac (3Ph+N+PE) | |||
Voltage regulation | ±1% | |||
Power factor | 1 | |||
Output frequency | Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) | ||
Bat. mode | 50/60 (±0.1%)Hz | |||
AC mode to Bat.mode | 0ms | |||
Transfer time | Inverter to Bypass | 0ms | ||
Output waveform | Pure Sinewave | |||
Crest factor | 3:01 | |||
Harmonic distortion (THDv) | ≤1% Linear load | |||
≤3% Non linear load | ||||
Overload | AC mode | ≤110%, last 60min; ≤125%, last 10min; ≤150%, last 1min;>150% turn to bypass immediately | ||
Bat.mode | ≤110%, last 10min; ≤125%, last 1min; ≤150%, last 5s;>150% shutdown UPS immediately | |||
EFFICIENCY | ||||
Efficiency | up to 94% | |||
BATTERY | ||||
Battery voltage | Standard unit | ±120Vdc (20pcs 12V9AH) (2×20pcs 12V9AH, | ||
3×20pcs | ±120Vdc (2×20pcs 12V9AH) | ±120Vdc (3×20pcs 12V9AH) | ||
12V9AH optional) | (3×20pcs 12V9AH optional) | |||
Long run unit | ±96 /±108 /±120 /±132 /±144Vdc | |||
Charge Current | Standard unit | 1.35A (2.7/4.05A optional) | 2.7A (4.05A optional) | 4.05A |
Long run unit | 20A Max. | |||
PHYSICAL | ||||
Dimension | Standard unit | 250×900×868mm | ||
W×D×H | Long run unit | 250×580×655mm | ||
Net weight | 136kg/77kg | 188kg/78kg | 239kg/79kg | |
ENVIRONMENTAL | ||||
Operating temperature | 0~40℃ | |||
Storage temperature | -25~55℃ | |||
Humidity range | 0~95% (non-condensing) | |||
Altitude | <1500m, derating required when>1500m | |||
Noise level | ≤55dB | ≤58dB | ||
STANDARDS | ||||
Safety | UL1778, CSA 22.2-107.3-14 | |||
EMC | FCC Part 15 Subpart B, ANSI C63.4 2014 | |||
Energy star | Energy star 2.0 | |||